×

Factorized power architecture with point of load sine amplitude converters

  • US 20030227280A1
  • Filed: 05/22/2003
  • Published: 12/11/2003
  • Est. Priority Date: 01/31/2002
  • Status: Active Grant
First Claim
Patent Images

1. A method of distributing power from an input source to a load, where the load may vary over a normal operating range, comprising:

  • using a first regulator to convert power from the input source at a source voltage, Vsource, and deliver a controlled DC voltage, Vf, to a factorized bus;

    using a voltage transformation module (“

    VTM”

    ) to convert power, via a transformer, from the factorized bus at an input voltage Vin, essentially equal to the voltage delivered to the bus, Vf, to a DC output voltage, Vout; and

    using in the VTM an essentially constant voltage gain, K=Vout/Vin, at a load current, Vout being less than Vin and the VTM having a time constant, TVTM;

    wherein the load is supplied with a voltage, VL, essentially equal to the output voltage of the VTM, Vout, which is regulated by the first regulator under control of a closed loop having a response time, TPRM;

    using a first capacitance, C1, connected across VL at the point of load to supply instantaneous current requirements of the load for a first time interval, T1, with a maximum voltage deviation, Δ

    VL1, of the nominal voltage, VL, required by the load;

    using a second capacitance, C2, connected across Vf at the VTM input to supply instantaneous current requirements of the VTM for a second time interval, T2, with a maximum voltage deviation, Δ

    Vf, of the nominal voltage, Vf, at the input of the VTM; and

    wherein T2

    TPRM>

    T1

    TVTM, C2/K2

    C1, and Δ

    Vf*K≦

    Δ

    VL1.

View all claims
  • 4 Assignments
Timeline View
Assignment View
    ×
    ×