×

Ground fault interrupters

  • US 3,879,639 A
  • Filed: 09/10/1973
  • Issued: 04/22/1975
  • Est. Priority Date: 01/04/1973
  • Status: Expired due to Term
First Claim
Patent Images

1. A neutral-to-ground fault detector for a distribution circuit to supply alternating current at about 60 Hz to a load, where the circuit includes line and neutral conductors extending to load-connection terminals, and where the neutral conductor has a ground connection, said neutral-to-ground fault detector including a differential current transformer having a core, primary windings forming current paths in series with said line and neutral conductors respectively, between said load-connection terminals and said ground connection of said neutral, said primary winding being arranged to produce mutually cancelling magnetic effects in the core due to load current carried thereby, and (a) multi-turn winding means on the core, means including a capacitor connected to said (multi-turn) winding means for producing resonance therein at a frequency substantially higher than 60 Hz, said core and said resonated winding means being formed to have a Q greatly in excess of unity at the resonant frequency, means for exciting said resonated winding within its pass band, (and) means for detecting the reduction of Q of the resonated winding resulting from a neutral-to-ground fault and means for detecting an abnormal rise in excitation of said resonated winding.

View all claims
  • 2 Assignments
Timeline View
Assignment View
    ×
    ×