×

Systems and methods for protection of components in electrical power delivery systems

  • US 9,898,062 B2
  • Filed: 07/28/2014
  • Issued: 02/20/2018
  • Est. Priority Date: 09/15/2010
  • Status: Active Grant
First Claim
Patent Images

1. A system to monitor and control a plurality of electric power generators in an electric power delivery system, the system comprising:

  • a system protection Intelligent Electronic Device (“

    IED”

    ) processor;

    a system protection IED computer-readable storage medium, comprising instructions executable on the system protection IED processor that enable the system protection IED to;

    analyze a plurality of time-synchronized measurements indicating conditions associated with the plurality of generators, wherein the plurality of time-synchronized measurements are generated based on a common time reference;

    determine a system-level protection action based upon the analysis of the plurality of time-synchronized measurements by;

    detecting a common-mode fault condition as a condition of one generator of the plurality of generators that affects operating conditions of another generator of the plurality of generators;

    determining operating conditions of the electric power delivery system based on the plurality of time-synchronized measurements;

    detecting the generator associated with the detected common-mode fault condition;

    comparing the operating conditions with predetermined acceptable operating conditions of the electric power delivery system;

    when a common-mode fault is detected and when the operating conditions are outside of the predetermined acceptable operating conditions, determining the system-level protection action to be disconnection of the generator associated with the detected common-mode fault; and

    ,when a common-mode fault is detected and when the operating conditions are within the predetermined acceptable operating conditions, determining that the system-level protection action on the generator associated with the detected common-mode fault is not required;

    based on the comparison of the operating conditions with the predetermined acceptable operating conditions, perform the system-level protection action by disconnecting the electrical generator associated with the common-mode fault; and

    evaluate response time of controls of the generator associated with the detected common-mode fault before disconnecting the generator associated with the detected common-mode fault.

View all claims
  • 2 Assignments
Timeline View
Assignment View
    ×
    ×